# HT Italia HT96U 1-100-1000A/1V AC Current Transducer Clamp

# HT Italia HT96U 1-100-1000A/1V AC Current Transducer Clamp

## Key Features At A Glance

-   Three selectable AC current ranges — 1 A, 100 A, and 1000 A full scale — with a 1 V AC output signal
-   Measuring range spans 1 mA up to 1200 A AC across the three selectable ranges
-   Maximum error of 2% of reading over a 40 Hz to 10 kHz frequency range
-   Overvoltage category CAT III 600 V, pollution degree 2 according to IEC 1010-1
-   Diode protection with dielectric strength of 5.5 kV at 50 Hz for 1 minute
-   Accepts conductors up to 54 mm diameter or bus bars of 35x35 mm or 50x12 mm
-   2 m output cable with Hypertac connector; operating temperature -10 to +50 °C

The HT Italia HT96U is a clamp-type AC current transducer that converts a measured alternating current into a proportional 1 V AC output signal. It provides three selectable full-scale ranges — 1 A, 100 A, and 1000 A — with corresponding measuring ranges of 0.001 to 1.2 A, 0.1 to 120 A, and 1 A to 1200 A AC, and applies output ratios of 1 mV/mA, 10 mV/A, and 1 mV/A respectively across those ranges.

A current transducer clamp couples around a conductor to sense the AC current flowing through it without breaking the circuit, presenting a scaled low-level output that a host instrument can read. The HT96U is also configured for power measurement: the conventional current direction P1 ⇒ P2 indicated by the arrow must be observed so that the sensed quantity carries the correct sign.

ValueTronics stocks and holds its own inventory in a 20,000 square foot secure warehouse at 1675 Cambridge Drive in Elgin, Illinois.

## Product Core & Specifications

Specification

Value

General Specifications

Selectable ranges

1A / 100A / 1000A AC

Measuring range

0.001 ÷ 1.2A / 0.1 ÷ 120A / 1A ÷ 1200A AC

Output signal

1V AC

Protection

By diodes

Ratio

1mV/mA – 10mV/A - 1mV/A

Max error

2% (of reading)

Internal load

1A=3kΩ; 100A=15Ω; 1000A=1.5Ω

External min load

100 times the internal load

Power measurement

Take care to keep the conventional direction P1 ⇒ P2 of the arrow

Frequency range

40Hz ÷ 10kHz

Pollution degree

2 according to IEC 1010-1

Dielectric strength

5,5 KV 50 Hz 1 min

Temperature range

\-10 ÷ +50 °C

Overvoltage category

CAT III 600V

Max cable diameter

54 mm

Max bus bars

35x35mm or 50x12mm

Dimensions

105 x 225 x 31 mm

Weight

720 g

Output connection

Cable 2m with Hypertac connector

Accuracy — 1A FS

1 ÷ 100mA — Precision in %rdg of output signal

±(3%rdg + 0.5mV)

1 ÷ 100mA — Phase difference

Not specified

100 ÷ 500mA — Precision in %rdg of output signal

±(2%rdg + 1mV)

100 ÷ 500mA — Phase difference

Not specified

500mA ÷ 1.2A — Precision in %rdg of output signal

±(1%rdg +1mV)

500mA ÷ 1.2A — Phase difference

<10 degrees

Accuracy — 100A FS

100mA ÷ 1A — Precision in %rdg of output signal

±(1%rdg + 1mV)

100mA ÷ 1A — Phase difference

Not specified

1 ÷ 10A — Precision in %rdg of output signal

±(0.5%rdg +0.5mV)

1 ÷ 10A — Phase difference

2 degrees

10 ÷ 120A — Precision in %rdg of output signal

±(0.5%rdg)

10 ÷ 120A — Phase difference

1 degrees

Accuracy — 1000A FS

1 ÷ 10A — Precision in %rdg of output signal

±(1%rdg + 0.5mV)

1 ÷ 10A — Phase difference

Not specified

10 ÷ 100A — Precision in %rdg of output signal

±(0.5%rdg +1mV)

10 ÷ 100A — Phase difference

1.5 degrees

100 ÷ 1200A — Precision in %rdg of output signal

±(0.5%rdg)

100 ÷ 1200A — Phase difference

1 degrees

> **Important:** For power measurement, maintain the conventional current direction P1 ⇒ P2 indicated by the arrow.

> **Important:** Overvoltage category CAT III 600V; pollution degree 2 according to IEC 1010-1; dielectric strength 5.5 KV 50 Hz 1 min.

> **Important:** The external minimum load must be at least 100 times the internal load (internal load: 1A=3kΩ; 100A=15Ω; 1000A=1.5Ω).

## About this New unit

This is a brand-new, factory-sealed unit, supplied exactly as it arrives from the manufacturer and backed by the full manufacturer warranty. For the exact configuration, available options, included accessories, or current lead time for your application, our Test Architects can confirm the details before you order.

ValueTronics supplies both new and used test and measurement equipment. New units ship factory-sealed, exactly as received from the manufacturer; every used unit is inspected and functionally verified in-house at our 20,000 sq ft secure facility in Elgin, Illinois before it ships. Our Test Architects can help you select the condition, calibration, and configuration that fit your application.

**Please review the Manufacturer's Data Sheet to verify published specifications. Feedback on this webpage is always welcome — please reach out to your Test Architect at any time for questions or concerns. Thank you, we truly appreciate you being our customer.**

## Details

- **Price:** 495.0 USD
- **Vendor:** HT Italia
- **Type:** Curr Probe
- **Tags:** Current Clamp, HT Instruments, Manufacturers, Other Equipment, product_manual_group_3, Product_new

## Variants

| Variant | Price | Available |
|---------|-------|-----------|
| Default Title | 495.00 USD | In stock |

## Images

- HT Italia HT96U 1-100-1000A/1V AC Current Transducer Clamp

---

> Source: [ValueTronics](https://valuetronics.com/products/ht96u-ht-instruments-current-clamp-new)
> Updated: 2026-06-20